| MPS™ | ![]() |
![]() | www.maxwright.co.uk/mps/ info@maxwright.co.uk |
| Martin Control Panels | Systems & Software | Search | MPS News | Instrumentation | Motor Control Centres | Busbar Systems | Documentation | Careers | Where We Are |
| Introduction | Construction | Busbar System | Fixed Pattern Sections | Withdrawable Pattern Sections | Forms Of Seperation | Certification |
| The busbar system has been designed and is manufactured in-house by Max Wright Limited, with main through bar ratings from 400 Amps to 4000 Amps, with the vertical plug-in busbar droppers rated from 400 Amps to 1600 Amps. Both the main through busbars and dropper busbars are installed in a 2mm press formed busbar chamber giving segregation from other panel sections. The busbar supports are moulded glass filled nylon and positioned to allow the plug-in connectors at 50mm increments. |
| The busbar system has been ASTA Tested at the Falcon Test Laboratory. Certificate |

© Max Wright Limited 2003. This HTML document and its contents must not be reproduced for any purpose without written permission.